AWG to mm² Conversion Chart for Solar Cable: Is 10 AWG the Same as 6 mm²?
- 1. AWG to mm² Conversion Chart for Solar Cable
- 2. How to Read AWG and mm² on a Solar Cable
- 3. Can 6 mm² Solar Cable Replace 10 AWG PV Wire?
- 4. How to Check Solar Cable Ampacity
- 5. How Cable Length Affects Voltage Drop
- 6. How to Check PV Connector Fit After an AWG to mm² Conversion
- 7. What to Include in a Solar Cable RFQ
10 AWG has a nominal conductor area of 5.26 mm². A 6 mm² solar cable therefore has about 14% more nominal conductor area. This AWG to mm² conversion answers the size question. Whether you can use the quoted cable also depends on the project specification, the cable rating, and the connector at each end.
Suppose your drawing calls for 10 AWG copper PV wire, but the supplier offers 6 mm² solar cable at a better price. Before approving the offer, use the chart below to check the size. Then compare the two products using the same installation conditions.

1. AWG to mm² Conversion Chart for Solar Cable
Find your wire gauge in the chart
The middle column gives the nominal conductor area for each AWG size. The last column gives a common metric size you might see on a quote. For example, 12 AWG converts to 3.31 mm², while a supplier may offer a standard 4 mm² cable for review.
AWG size | Nominal conductor area | Metric cable size for comparison |
14 AWG | 2.08 mm² | 2.5 mm² |
12 AWG | 3.31 mm² | 4 mm² |
10 AWG | 5.26 mm² | 6 mm² |
8 AWG | 8.37 mm² | 10 mm² |
6 AWG | 13.30 mm² | 16 mm² |
4 AWG | 21.15 mm² | 25 mm² |
2 AWG | 33.62 mm² | 35 mm² |
Read the AWG to mm² chart in reverse
What if your drawing specifies 6 mm² and the supplier offers 10 AWG? In that direction, the offer reduces the nominal conductor area from 6 to 5.26 mm², a decrease of about 12%. The percentage changes because the starting size changes. Record the specified size and the offered size in separate columns when comparing bids.

2. How to Read AWG and mm² on a Solar Cable
Decode the cable jacket and the quotation
On a cable marked 10 AWG PV Wire, the gauge tells you the conductor size. The rest of the jacket marking can answer questions that the gauge alone leaves open. For example, an FRCABLE bare-copper PV wire datasheet shows the product type, UL file number, voltage rating, and wet and dry temperature ratings. You can compare those details with the approved cable schedule when the drums arrive.
A quote reading 1 × 6 mm² tells you that the cable has one core with a nominal conductor area of 6 mm². Look separately for the finished cable diameter, which the datasheet gives in mm. This distinction matters when ordering connectors because the contact grips the conductor while the seal fits around the cable insulation.
3. Can 6 mm² Solar Cable Replace 10 AWG PV Wire?
Use the AWG to mm² result to review the quote
A 6 mm² cable may be suitable if the project permits an alternative and the exact product meets its requirements. Start by requesting the manufacturer’s part number. For example, FRCABLE lists bare-copper, tinned-copper, and aluminum PV wire families. A description such as “6 mm² solar cable” leaves the conductor material open.
Consider a project that specifies 10 AWG copper PV wire to UL 4703. Here is how a buyer can review a shorter supplier quote.
Project requirement | Supplier’s quote | Detail to request |
10 AWG copper conductor | 1 × 6 mm² | Conductor material and exact cable part number |
UL 4703 PV wire | Solar cable | Listing information covering the offered product |
Minimum 1,500 V DC | Voltage omitted | Rated voltage and a sample jacket marking |
Connector specified on drawing | Connectors included | Manufacturer and part number at each end |
Ask the supplier to price the specified cable and the alternative on separate lines. Purchasing can then compare costs while the project engineer reviews the proposed change.

4. How to Check Solar Cable Ampacity
Compare ratings under the same installation conditions
Ampacity is the current a conductor can carry under specified conditions. Before comparing two amp ratings, check the conductor material, ambient temperature, installation method, and number of grouped current-carrying conductors. Also check the temperature rating of the connected equipment. That rating can limit the allowable current.
For example, one supplier may quote an amp rating for a cable in free air. Another may assume the cable runs through conduit. Ask both suppliers which conditions they used. Then enter the project conditions into the FRCABLE Ampacity Calculator for a preliminary comparison.
5. How Cable Length Affects Voltage Drop
Calculate the full DC circuit length
An AWG to mm² chart gives you the conductor area. To estimate voltage drop, you also need the current, the cable resistance, and the length of the circuit. For a two-wire DC circuit, include both the outgoing and return conductors. Use the cable resistance at the temperature you are assessing.
For example, suppose a 600 V DC circuit carries 15 A over a 50 m one-way route. For this example, assume each conductor has a resistance of 3.5 Ω/km at the operating temperature.
Step | Calculation | Result |
Add the outgoing and return lengths | 50 m + 50 m | 0.10 km |
Find the loop resistance | 0.10 km × 3.5 Ω/km | 0.35 Ω |
Calculate cable voltage drop | 15 A × 0.35 Ω | 5.25 V |
Express the drop as a percentage | 5.25 V ÷ 600 V × 100 | 0.88% |
If you enter 50 m as the total conductor length, your result will be half the actual cable drop in this example. Before using a calculator, check whether it asks for one-way length or loop length. For other run lengths, see the FRCABLE Voltage Drop Tables.
6. How to Check PV Connector Fit After an AWG to mm² Conversion
Match the conductor to the contact and the cable to the seal
First, check whether the crimp contact accepts the conductor size and construction. Next, compare the finished cable diameter with the seal range for the exact connector part number. Even within one connector family, two sockets can accept the same conductor size and have different seals.
For example, Stäubli lists two MC4-Evo 2 sockets with entries for both 6 mm² and 10 AWG under their respective approval columns. Here is how the choice changes for a cable with a 7.0 mm outside diameter.
Stäubli socket part number | Permitted cable outside diameter | Does 7.0 mm fall within the range? |
32.0316P0001 | 4.7–6.4 mm | No |
32.0318P0001 | 5.9–7.3 mm | Yes |
The second socket passes this diameter check. To complete the review, check the cable’s full diameter tolerance and the other conditions for that connector. The manufacturer publishes the dimensions by order number in the S
7. What to Include in a Solar Cable RFQ
Give suppliers one specification to quote against
List the conductor size and material, required cable standard, DC voltage rating, quantity by colour, and drum length. For terminated leads, include the finished assembly length and the connector part number at each end. If you accept alternatives for review, ask suppliers to identify each change on a separate quotation line.
Copy this request for a 10 AWG solar cable quote
Please quote 10 AWG copper PV wire to UL 4703 for the attached cable schedule. The schedule lists our DC voltage rating, quantities by colour, and required drum lengths.Please include the cable part number, datasheet, listing information, outside diameter with tolerance, and maximum DC conductor resistance at 20°C.If you offer a 6 mm² alternative, please price it separately and identify each difference from the specified cable. For assembled leads, please also provide the connector manufacturer and part number at each end.
With those details on the quote, the project engineer can review the substitution, the buyer can compare prices, and the receiving team knows which marking to look for on each drum.