
Ampacity Calculator
The purpose of this calculator is to determine the ampacity of conductors in conduit, cable, or directly buried. All calculations are based on the National Electrical Code®.
Information about the ampacity calculation methodology and code requirements is included below the calculator.
Ampacity Calculator: Detailed Information & Instructions
This application determines the allowable ampacity of insulated conductors and specific cable-type wiring methods (up to 2000V) based on the 2017 and 2020 National Electrical Code (NEC®).
1. Core Methodology
Calculations are based on NEC® Table 310.15(B)(16). The calculator assumes conductors are installed in a conduit or are direct-buried.
-
Metal Type: Calculations vary significantly by material. For example, 3/0 AWG Copper has an ampacity of 200A at 75°C, whereas 3/0 AWG Aluminum is rated at 155A at 75°C.
-
Insulation Rating: Common types (THHN/THWN-2, XHHW-2, and USE-2/RHH/RHW-2) are rated at 90°C. This 90°C rating serves as the starting point for applying correction and adjustment factors.
2. Temperature & Termination Limits
The final ampacity is often limited by the "weakest link" in the circuit—usually the equipment terminals or the cable jacket.
-
Equipment Terminations (NEC 110.14(C)(1)): * 14 AWG to 1 AWG: Assumed connection to equipment limited to 60°C.
-
1/0 AWG and larger: Assumed connection to equipment limited to 75°C.
-
Note: Standard 600V panelboards are typically limited to 75°C.
-
-
Cable-Specific Limits:
-
Type NM-B & UF-B: Limited to the 60°C column, even if the internal wire insulation is 90°C.
-
Type SER, SEU, & MC: Generally limited to 75°C.
-
-
Manufacturing Constraints: NM-B is permitted up to 2 AWG, while multiconductor UF-B is limited to 6 AWG per UL standards.
3. Ambient Temperature Correction
The base ratings in Table 310.15(B)(16) assume an ambient temperature of 86°F (30°C).
-
If the temperature exceeds 86°F, or falls below 78°F, ampacity must be corrected using factors from NEC Table 310.15(B)(2)(a).
4. Adjustment for Current-Carrying Conductors
Bundling multiple conductors creates heat. Table ratings assume a maximum of three current-carrying conductors.
-
For 4 or more conductors, adjustment factors from NEC Table 310.15(B)(3)(a) apply.
-
Factors: Range from 80% (for 4–6 conductors) down to 35% (for 41+ conductors).
-
Counting Rules: Include "spare" conductors; do not include equipment grounding conductors (EGC) or neutral conductors that meet NEC 310.15(B)(5) exceptions.
5. Parallel Runs
Running multiple conductors in parallel is permitted only for sizes 1/0 AWG or larger.
-
The "number of parallel runs" refers to the separate conductors per phase or polarity.
-
Installation must comply with the strict requirements of NEC 310.10(H).
6. Output & Logic
The calculator ensures safety by selecting the minimum (most conservative) value among:
-
The Corrected and Adjusted Ampacity (based on temperature and bundling).
-
The Equipment Termination Limit (per NEC 110.14(C)(1)).
-
The Cable Type Limit (e.g., the 60°C cap for NM-B).
